Print Back
FO 510 Industrial Oil Moisture Sensors
Unit of Measure
Items FO 510 Industrial Oil Moisture Sensors
0699 0100
FO 510 Industrial Oil Moisture Sensor
Web Price Quote
Description N/A FO 510 for moisture measurement in technical oils
Approve Payments N/A Finance with Approve Payments

Humidity Measuring Range N/A 0 to 1 aw
Accuracy (±) at 73 Degree Fahrenheit (ºF) Temperature and 0 to 0.9 Water Activity (aw) Humidity Measuring Range N/A 0.02 aw
Typical Accuracy (±) at 73 Degree Fahrenheit (ºF) Temperature and 0.9 to 1.0 Water Activity (aw) Humidity Measuring Range N/A 0.03 aw
Temperature Measuring Range N/A 0 to 257 ºF
Temperature Accuracy N/A +0.3 ºC
Oil Temperature N/A -20 to +257 ºF
Ambient Temperature N/A -20 to +158 ºF
Pressure Range N/A Up to 4351 psi
Interfaces N/A 2 x Analogue Output 4 to 20 mA (3-Wire-Technology) Modbus RTU (RS 485)
Direct Current (DC) Voltage N/A 10 to 36 V24 V
Protection Class N/A IP 66
Electromagnetic Compatibility (EMC) N/A In According with DIN EN 61326-1
Material Thread N/A 1.4404
Material Perforated Cap N/A 1.4301
Connection N/A M12
Number of Connection Pins N/A 8
Special Advantages N/A
  • Fast response time
  • Highly accurate measurement of water activity (aw), as well as process temperature. Measurement is independent of the respective oil type or age
  • Calculation of the absolute water content (PPM), possible for transformer oil
  • Two configurable analogue outputs, as well as Modbus-RTU (RS 485) interface available
Typical Applications N/A Measurement of residual moisture in:
  • Transformer oil
  • Engine oil
  • Lubricating oil
  • Hydraulic oil
  • Diesel fuels